Victron Energy | Cerbo GX Failure Immediately After Initial Commissioning

13.06.2025
Victron Energy | Cerbo GX Ausfall direkt nach der Erstinbetriebnahme

Certain Cerbo GX batches from 2023 have a power-supply design issue that can cause failure in some 48 V systems. In most cases the fault occurs immediately when the device is powered, for example during wiring, when inserting the fuse and/or when switching on the system. A faulty Cerbo can be replaced under warranty. To prevent the problem from recurring, a capacitor must be installed. Please contact support if your system is affected. Current units do not have this issue.